Product
(주)위슨테크놀로지 제품을 소개합니다.

Solution
제품 관련 솔루션 내용을 보실 수 있습니다.

MX 시리즈 AC/DC 전원공급기 [AMETEK] 파워서플라이
The California Instruments MX Series consists of multiple high power AC and DC power systems that provide controlled AC and DC output for ATE and product test applications.
California Instruments MX Series :
Specifications
|
Operating Modes | |
|
Standard |
AC or DC |
|
Pi Version |
AC, DC and AC+DC |
|
AC Mode Output | |
|
Frequency |
Range: 16.00-819.0 Hz, -LF
Option: 16.00-500.0 Hz, -HF Option: 16.00-905 Hz (supplemental specifications
apply above 819 Hz). Resolution: 0.01 Hz: 16.00 - 81.91 Hz, 0.1 Hz: 82.0 Hz -
819.1 Hz, |
|
Phase Outputs |
MX15-1/15-1Pi: 1,
MX22.5/30/45-3Pi: 1 or 3 switchable, Neutral: Floating, Coupling: DC (except
for -HV option) |
|
Total Power |
MX15-1/1Pi: 15 kVA,
MX22.5-1/3 : 22.5 kVA, MX30-1/3: 30 kVA, MX45-1/3: 45 kVA, MX90: 90 kVA,
MX135: 135 kVA |
|
Load Power Factor |
0 to unity at full output
current |
|
AC Mode Voltage | |||
|
Voltage Ranges | |||
|
Range |
VLow |
VHigh | |
|
AC |
0-150 V |
0-300 V | |
|
AC+DC |
0-150 V |
0-300 V | |
|
Load Regulation |
< 0.25 % FS DC to 100 Hz,
< 0.5 % FS 100 Hz to 819 Hz | ||
|
Line Regulation |
< 0.1% FS for 10 % line
change | ||
|
External Sense |
Voltage drop compensation
(5% Full Scale) | ||
|
Harmonic Distortion (Linear) |
Less than 0.5% from 16 - 66
Hz, Less than 1% from 66 - 500 Hz, Less than 1.25% above 500 Hz | ||
|
DC Offset |
< 20 mV | ||
|
External Amplitude
Modulation |
Depth: 0 - 10 %, Frequency:
DC - 2 KHz | ||
|
Voltage slew rate |
200 μs for 10% to 90% of
full scale change into resistive load | ||
|
AC Mode Current | |||
|
Models |
Steady State AC Current @ FS
V | ||
|
V Low |
V High | ||
|
MX15-1 |
100 |
50 | |
|
MX15-1Pi |
100 |
50 | |
|
MX22.5-3Pi / 1Pi |
50/ø / 150 |
25/ø / 75 | |
|
MX30-1 |
200 |
100 | |
|
MX30-3 |
66.6/ø |
33.3/ø | |
|
MX30-3Pi / 1Pi |
66.6/ø / 200 |
33.3/ø / 100 | |
|
MX45-1 |
300 |
150 | |
|
MX45-3 |
100/ø |
50/ø | |
|
MX45-3Pi / 1Pi |
100/ø / 300 |
50/ø / 150 | |
|
MX90-3/Pi |
200/ø |
100/ø | |
|
MX135-3/Pi |
300/ø |
150/ø | |
|
Note: Constant power mode
provides increased current at reduced voltage. See chart below | |||
|
Peak Repetitive AC Current |
Up to 3.6 x rms current at
full scale voltage | ||
|
Programming Accuracy |
Voltage (rms): ± 0.3 Vrms,
Frequency: ± 0.01 % of programmed value, Current Limit: - 0 % to + 5 % of
programmed value + 1A, Phase: < 0.5° + 0.2°/ 100 Hz with balanced load | ||
|
Programming Resolution |
Voltage (rms): 100 mV,
Frequency: 0.01 Hz from 16 - 81.91 Hz, 0.1 Hz from 82.0 - 819 Hz, Current
Limit: 0.1 A, 3 phase mode, 1.0 A, 1 phase mode, Phase: 0.1° | ||
|
Constant Power AC Mode |
|
|
|
Measurements - Standard | |||
|
Parameter |
Range |
Accuracy* (±) |
Resolution* |
|
Frequency |
16-100 Hz |
0.01% + 0.01 Hz |
0.01 Hz / 0.1 Hz |
|
RMS Voltage |
0-400 V |
0.05 V + 0.02% |
10 mV |
|
RMS Current |
0-160 A |
0.15 A + 0.02% |
10 mA |
|
Peak Current |
0-400 A |
0.15 A + 0.02% |
10 mA |
|
Crest Factor |
0.00-6.00 |
0.05 |
0.01 |
|
Real Power |
0-15 kW |
30 W + 0.1% |
10 W |
|
Apparent Power |
0-15 kVA |
30 VA + 0.1% |
10 VA |
|
Power Factor |
0.00-1.00 |
0.01 |
0.01 |
|
Phase |
0.0-360.0 |
2.0° |
0.1° |
|
DC Voltage |
0-400 V |
0.5 V |
10 mV |
|
DC Current |
0-160 A |
0.5 A |
10 mA |
|
Power |
0-15 kW |
0.15 kW |
10 W |
|
* Measurement system
bandwidth = DC to 6.7 kHz. Accuracy specifications are valid above 100
counts. Current and Power Accuracy and Range specifications are times three
for MX90, MX135 or MX30/45-3Pi in single phase mode. PF accuracy applies for
PF > 0.5 and VA > 50 % of range | |||
|
Measurements - Harmonics (Pi
controller only) | |||||||
|
Parameter |
Frequency Fundamental
Harmonics |
Phase |
Voltage |
Current | |||
|
Range |
16.00-1000.0 Hz / |
0.0 - 360.0° |
Fundamental |
Fundamental | |||
|
Accuracy* (±) |
0.03% + 0.03 Hz / |
2° typ. |
750 mV 0.3% + 750 |
0.5 A / 0.3% + 150 mA | |||
|
Resolution |
0.01 Hz |
0.5° |
10 mV / 10 mV |
100 mA / 100 mA | |||
|
* Accuracy specifications
are valid above 100 counts. Accuracy specifications are for three phase mode.
Harmonics frequency range for MX30/45-3Pi in single phase mode is 32 Hz - 48
kHz | |||||||
|
DC Mode Output | |||||||
|
Power |
Max DC power at full scale
of DC voltage range. MX15-1Pi: (10 kW), MX22.5-3Pi : (5 kW per output, 3
outputs. 15 kW in 1 channel mode, MX30-3Pi: (6.5 kW per output, 3 outputs. 20
kW in 1 channel mode), MX45-3Pi: (10 kW per output, 3 outputs. 30 kW in 1 channel
mode) | ||||||
|
Voltage Ranges |
Low (0 - 200 V), High (0 -
400 V) | ||||||
|
Output Accuracy |
± 1 Vdc | ||||||
|
Load Regulation |
< 0.25 % FS | ||||||
|
Line Regulation |
< 0.1% FS or 10 % line
change | ||||||
|
Ripple |
< 2 Vrms Lo Range, < 3
Vrms Hi Range | ||||||
|
Current Limit |
Programmable from 0 A to
max. current for selected range. | ||||||
|
Max DC Current @ FSV per
output | |||||||
|
Model |
V Low |
V High | |||||
|
MX15-1 |
50 |
25 | |||||
|
MX15-1Pi |
50 |
25 | |||||
|
MX22.5-3Pi / 1Pi |
25 / 75 |
12.5 / 37.5 | |||||
|
MX30-1 |
100 |
50 | |||||
|
MX30-3 |
33.3 |
16.6 | |||||
|
MX30-3Pi / 1Pi |
33.3 / 100 |
16.6 / 50 | |||||
|
MX45-1 |
150 |
75 | |||||
|
MX45-3 |
50 |
25 | |||||
|
MX45-3Pi / 1Pi |
50 / 150 |
25 / 75 | |||||
|
MX90-3/Pi |
100 |
50 | |||||
|
MX135-3/Pi |
150 |
75 | |||||
|
AC+DC Mode Output | |
|
Output Power (Pi only) |
Maximum current and power in
AC+DC mode is same as DC mode |
|
Protection | |
|
Over Load |
Constant Current or Constant
Voltage mode |
|
Over Temperature |
Automatic shutdown |
|
Storage | |
|
Non Volatile Mem. storage |
16 instrument setups, 200
user defined waveforms [Pi only] |
|
Waveforms | |
|
Waveform Types |
Std: Sine, Pi: Sine, Square,
Clipped sine, User defined |
|
User defined waveform |
Four groups of 50 user
defined arbitrary waveforms of 1024 points for a total of 200. One group can
be active at a time |
|
System Interface | |
|
Inputs |
Remote shutdown, External
Sync, Clock/Lock (option on Pi) |
|
Outputs |
Function Strobe / Trigger
out, Clock/Lock (option on Pi) |
|
Remote Control (Pi
only/standard with -P option) | |
|
IEEE-488 Interface |
IEEE-488 (GPIB) talker
listener. Subset: AH1, C0, DC1, DT1, L3, PP0, RL2, SH1, SR1, T6, IEEE-488.2
SCPI Syntax |
|
RS232C Interface |
9 pin D-shell connector
(Supplied with RS232C cable) |
|
Output Relay |
Push button controlled or
bus controlled output relay |
|
Output impedance |
Programmable Z available on
MX30-3Pi and MX45-3Pi in 3 phase mode only. Specifications apply at 50 Hz
fundamental. Resistive: 1 - 200 mOhm, Inductive: 170 - 200 uH |
|
AC Input | |||
|
Voltage |
Must be specified at time of
order. All inputs are L-L, 3ø, 3 wire + Gnd. 208 ± 10% VAC, 230 ± 10% VAC,
400 ± 10% VAC, 480 ± 10% VAC | ||
|
Input Line Current (per
phase) | |||
|
Current (MX15) |
V L-L |
St State | |
|
208 |
58.3 ARMS | ||
|
230 |
52.3 ARMS | ||
|
400 |
30 ARMS | ||
|
480 |
25 ARMS | ||
|
Current (MX22.5/30/45) |
V L-L |
St State | |
|
208 |
89/116/175 ARMS | ||
|
230 |
79/105/157 ARMS | ||
|
380 |
49/64/95 ARMS | ||
|
400 |
46/60/90 ARMS | ||
|
480 |
38/50/75 ARMS | ||
|
Distortion: < 8 % at full
power < 20 % below 35 % of power | |||
|
Line Frequency |
47 - 63 Hz | ||
|
Efficiency |
85 % typical | ||
|
Power Factor |
0.95 typical | ||
|
AC Service | |
|
Inputs/Outputs |
MX30/MX45: Front access,
cables routed through rear panel, exit in back. MX15: Rear Access |
|
Regulatory |
IEC61010, EN50081-2,
EN50082-2, CE EMC and Safety Mark requirements |
|
EMI |
CISPR 11, Group1 , Class A |
|
Connectors |
AC Input & Output
terminal block behind front cover, IEEE-488 (GPIB) connector (rear panel), 9
pin D-Shell RS232C connector*, (rear panel), Remote voltage sense terminal
block (rear panel), System Interface Connector, DB-37 (rear panel). *RS232
DB9 to DB9 cable supplied |
|
Physical Dimensions | |
|
MX30/MX45 Dimensions |
Height: 50.0” (1270 mm), Width: 28.75” (731 mm), Depth:
34.5” (876 mm) |
|
MX30/MX45 Weight |
Chassis: Net: 1150 lbs / 522 Kg, Shipping: 1231 lbs /
560 Kg, Amp Module: Net: 63 lbs / 29 Kg |
|
MX15 Dimensions |
Height: 31.75” (806 mm), Width: 24.0” (610 mm), Depth:
28.0” (711 mm) |
|
MX15 Weight |
Chassis: Net: 600 lbs / 272 Kg, Shipping: 681 lbs / 309
Kg, Amp Module: Net: 63 lbs / 29 Kg |
|
Chassis |
MX30/MX45: Casters and forklift openings. MX15: Casters |
|
Vibration and Shock |
Designed to meet NSTA project 1A transportation levels.
Units are shipped in wooden |
|
Air Intake/Exhaust |
Forced air cooling, front air intake, rear exhaust |
|
Operating Humidity |
0 to 95 % RAH, non condensing |
|
Temperature |
Operating: 0 to 40° C (30° C max in CP mode), Storage:
-20 to +85° C |
Standard controller versions with single voltage range | ||||
| Model | AC Output Power | Phase Outputs | AC/DC Voltage Range | Controller |
| MX15-1 | 15kVA | 1 | 150/200 & 300/400 | Standard |
| MX30-1 | 30 kVA | 1 | 150/200 & 300/400 | Standard |
| MX30-3 | 30 kVA | 3 | 150/200 & 300/400 | Standard |
| MX45-1 | 45 kVA | 1 | 150/200 & 300/400 | Standard |
| MX45-3 | 45 kVA | 3 | 150/200 & 300/400 | Standard |
| MX90-3 | 90 kVA | 3 | 150/200 & 300/400 | Standard |
| MX135-3 | 135 kVA | 3 | 150/200 & 300/400 | Standard |
| Programmable controller versions with dual voltage ranges | ||||
| Model | AC Output Power | Phase Outputs | AC/DC Voltage Range | Controller |
| MX15-1Pi | 15kVA | 1 | 150/200 & 300/400 | Programmable |
| MX30-3Pi | 30 kVA | 1 & 3 | 150/200 & 300/400 | Programmable |
| MX45-3Pi | 45 kVA | 1 & 3 | 150/200 & 300/400 | Programmable |
| MX90-3Pi | 90 kVA | 3 | 150/200 & 300/400 | Programmable |
| MX135-3Pi | 135 kVA | 3 | 150/200 & 300/400 | Programmable |
| Pi models include IEEE-488 and RS232C interfaces, Advanced measurements, arbitrary waveform generation. Phase mode switching on MX-30/45-3Pi. | ||||
| Reconfigurable Power Systems | ||||
| Model | AC Output Power | Phase Outputs | AC/DC Voltage Range | Controller |
| MX90-3Pi-MB | 90 kVA | 3 | 150/200 & 300/400 | Dual MX45-3Pi |
| MX135-3Pi-MB | 135 kVA | 3 | 150/200 & 300/400 | Triple MX-45-3Pi |
| Reconfigurable systems can be separated into stand-alone MX45-3Pi models or combined for higher power levels. | ||||
| Controller Options | |
| Specify output range on standard models. All range values shown are Line to Neutral. | |
| Option Code | Description |
| -150 | Configured for 150 V AC and 200 V DC output ranges. |
| -300 | Configured for 300 V AC and 400 V DC output ranges. |
| -LF | Limits maximum frequency to 500 Hz. |
| -FC | Modifies output frequency control to ± 0.25% |
| -P | IEEE-488 and RS232C Interface option. Adds programming, Windows software and RS232 Cable. |
| -HF | Increases maximum frequency to 905 Hz. |
| -R | Range change. Provides both 150/200 and 300/400 AC/DC output ranges (Std. on MX15). |
| Pi Model Options | |
| Option Code | Description |
| -411 | *IEC 1000-4-11 test firmware. |
| -413 | *IEC 1000-4-13 Harmonics & Interharmonics test firmware. |
| -HV | Adds 400 V AC-only output range |
| -LF | Limits max. frequency to 500 Hz |
| -HF | Increases max. frequency to 1000 Hz |
| -XV | Adds other AC-only output range. Consult factory |
| -LKM | Clock/Lock Master |
| -LKS | Clock/Lock Auxiliary |
| -WHM | Watt-Hour Measurement option |
Note: See Avionics brochure for details * Not applicable on MX15 | |
| Avionic Test Routine Options | |
| -ABD | ABD0100.1.8 Test Option. |
| -AMD | Airbus AMD24 Test |
| -A350 | Airbus Test Software |
| -B787 | Boeing 787 Test Software |
| -160 | RTCA/DO-160D, DO-160E, and EUROCAE test firmware. |
| -704 | Mil Std 704 A - F test - firmware/ software. |
| * Note Reference the Avionics Test User Manual P/N 4994-971 for a complete listing of performance capabilities. | |
| AC Mode Current | |||
| Models | Std | Pi | |
| AC mode | X | X | |
| DC mode | X | X | |
| AC+DC mode | - | X | |
| Dual V Range | Option (Std / MX15) | X | |
| Transient programming | X | X | |
| Arbitrary waveforms | - | X | |
| Measurements | X | X | |
| Harmonic measurements | - | X | |
| Waveform acquisition | - | X | |
| 1 or 3 Phase mode | - | MX30/45-3Pi | |
| IEEE / RS232 | Option | X | |
| Options | |
| Model | Refer to table shown for model numbers and configurations |
| Supplied with | |
| Standard | User Manual on CD ROM. |
| Pi version | User/Programming Manual and Software on CD ROM. RS232C serial cable. |
| Packaging and Shipment |
| All MX systems are packaged in re-usable protective wooden crates for shipment. |

다운로드
가정용 PCS 데이터모니터링 시스템 구축• 설비 개요 : - 유럽향 모델의 가정용 PCS 제품이 개발 완료, 수출 국가별(향지 별) PCS의 새로운 모델이 지속적으로 개발/출시 예정. - 개발 예정 모델의 경우 PCS의 제어 인터페이스가 변경 될 수 있고 이로 인해 새 모델마다 PCS 데이터 수집 장치 개발을 위한 리소스가 투입 필요. - 개발완료 및 출시 예정 모델의 장시간 AGING 시험 및 데이터 취득을 자동화 함. - 적용모델 : 가정용 5KW, 8KW, 10KW - 향후 적용예정 모델 : 북미향 올인원 가정용 ESS PCS 등• 납품처 : LG전자 ESS품질보증파트, ESS PCS 개발팀• 설비 특징 및 장점 : - 새로운 모델의 개발/출시 시 PCS제어 인터페이스가 변경될 수 있고 이로 인해 새 모델마다 PCS 데이터수집 장치 개발을 위한 리소스 투입 필요. - PCS 모델 별로 필요한 측정 아이템을 사용자가 직접 편집하고 파일 기반으로 저장, 관리 할 수 있는 기능을 구축하여 새로운 모델에 대한 데이터 취득 시스템 리소스 투자 비용 감소. - 기 양산 모델 뿐만 아니라 개발 예정 PCS제품들에 동일한 인터페이스를 이용하여 제품 모델에 관계없이 PCS의 데이터를 모니터링, 레코딩 할 수 있는 기능을 지원함.
자세히 보기
가정용 ESS PCS 인정 시험 시스템 구축• 설비 개요 : - 유럽향 가정용 ESS PCS 모델의 다양한 계통환경 및 온습도 환경에 대한 모의 및 PCS 인정 시험. - 배터리모의전원, 계통모의전원, PV모의전원, 전력분석기, 온도시험챔버,온도레코더 및 PCS를 직접 제어하여 시험 수행. - PCS의 EVENT 발생 시 Event 시간의 전력 및 온도데이터의 Database 화 및 Post-Processing - 적용모델 : 가정용 5KW, 가정용 8KW, 가정용 10KW - 적용예정모델 : 북미향 올인원 PCS• 납품처 : LGE ESS품질보증파트, ESS PCS 개발팀. • 설비 장점 : - PMS를 제어하여 PCS의 충전/방전 등을 직접 제어하여 PCS 출력에 따른 다양한 계통환경 및 온도 환경을 동기화 제어. - PCS Event(Alarm, Error) 발생 시 Event 전/후 데이터의 고속 데이터 자동 취득으로 Event 전/후 전력아이템, 온도 등의 데이터를 동기화 기록. - Event 전/후 고속 데이터 및 상시 운전 데이터를 데이터 베이스 이원화로 구축하여 데이터 관리 및 Post-Processing의 편의성 제공.